3 Phase Power & Harmonic Analyser - DW6095

Write a review
51,370,000 تومان
31131
Out of stock

Power quality check, power parameters, phase diagram, harmonics and transients

AC parameters, Power Factor, Phase, Harmonics ,Crest Factor, Active, Apparent, Reactive Power

Peak AC voltage and current *IEC 1010 CATIII 600V

includes 3 x 1200 amp current clamps - optional 3000amp flexible style

Real time logger 2 seconds to 7200 seconds - to SD card

Transients recorded such as dip, swell and outage with programmable threshold (not waveform)

Display waveform, harmonics, Total harmonic distortion, phase diagram

export recorded data direct via SD card to EXCEL software for analysis

3 Phase Power Analyser Lutron DW-6095 brings basic power analysis, and fault finding within the grasp of most technicians. For a modest price the user gets a complete, ready to use kit for measuring all power parameters on industrial installations to 1200amps, with extension using clamp CP3000 to 3000 amps. Whilst it is not as powerful, fast or sophisticated as some of the market leaders, the tool brings it functions to the user at 20% of the existing prices. Using the DW-6095 you can determine the peak power requirements, correct power factor problems, balance phases and identify supply faults such as wave form distortion, harmonics, breaks and surges.

Power quality problems can cost you big money.

Power can be lost through changes in power factor through different boards in your plant, or different phases in a board. You can suffer from very high tariff rates being applied based on short term peak loading. The first step to making a decision on the best action plan, is to find out what is happening in your plant power system.

The Lutron DW-6095 provides the most functionality of all the simple power analyzers with up to 35 parameters to 600VAC and 1200 amps – or 3000amps with the optional flexible current probes. It includes harmonics to 50th order and captures transient events [non graphically] as dips, swells and outage with a response time around 130microseconds. Data can be logged at intervals from 2 second to 7200 seconds with 30000 sets of 9 parameters per block, on a 2GB SD card – for ready analysis in a spread sheet.

The unit comes as a complete kit with current (x 3) and voltage probes (x 4) in a carry bag ready for use.

CP-3000 flexible current probes for 30, 300, and 3000amp [selectable] are optional for the DW-6095 and connect directly without separate power supply.

For a lower cost solution there is model DW-6093 that has no Phase graphics and no transient detection. It has the same capability for measurements and logging

The information gained through a plant-wide review with this instrument will guide you in planning steps to reduce your power consumption, and certainly your power bills in future. For more information contact ECEFast.

 

introduces the Lutron DW-6095 power analysers designed for affordable power analysis of factory equipment.

ECEF ast is one of Australia’s leading suppliers of industrial instrumentation and specializes in handheld industrial instruments for power analysis.   Power quality problems can prove expensive for manufacturing businesses.

Power can be lost through changes in power factor on different boards in the plant or different phases in a board. Manufacturing facilities can also suffer from very high tariff rates being applied based on short term peak loading.

Information gained through a plant-wide review using Lutron DW-6095 power analysers can guide manufacturing businesses in planning steps to reduce power consumption and increase overall efficiency.

Key features of Lutron DW-6095 power analyzers:

Provides high functionality with up to 35 parameters to 600VAC and 1,200 amps or 3,000 amps with optional flexible current probes

Includes harmonics to 50th order and captures transient events such as dips, swells and outage

Data can be logged at intervals from 2 to 7200 seconds with 30,000 readings on a 2GB SD card

Comes as a complete kit with 3 current and 4 voltage probes in a carry bag ready for use

Optional flexible current probes (CP-3000) for 30, 300, and 3000 amp also available to connect directly

 

 

 

3 Phase Power Analyser Lutron DW-6095 brings basic power analysis, and fault finding within the grasp of most technicians. Included is a complete, ready to use kit for measuring all power parameters on industrial installations to 1200A, with extension using clamp CP3000 to 3000A.

 

Power quality problems can cost manufacturing businesses big money and power can be lost through changes in power factor on different boards in your plant or different phases in a board. Facilities can also suffer from very high tariff rates being applied based on short term peak loading. Before determining the best action plan for your operations to minimize this, find out what is happening in your plant power system.

 

The Lutron DW-6095 provides the most functionality of all the simple power analyzers with up to 35 parameters to 600VAC and 1, 200A or 3, 000A with optional flexible current probes. It includes harmonics to 50th order and captures transient events as dips, swells and outage. Data can be logged at intervals from 2 to 7200 seconds with 30, 000 readings on a 2GB SD card for ready analysis in a spread sheet format.

 

The unit comes as a complete kit with 3 current and 4 voltage probes in a carry bag ready for use. Flexible current probes ( CP-3000) for 30, 300, and 3000A are also available as an optional extra for the DW-6095 and connect directly without separate power supply.

 

The information gained through a plant-wide review with this instrument can guide you in planning steps to reduce your power consumption, and certainly your power bills in future.

 

Features

 

Analysis for 3 phase multi-power system, 1P/ 2W, 1P/ 3W, 3P/ 3W, 3P/ 4W

3 current probes ( CP-1201) are included, if change the current probes, the calibration procedures are not necessary

Current probe input signal/ ranges with selection: 

 

Input Signal ( ACV) 

 

200mV / 300mV / 500mV / 1V / 2V / 3V

 

Ranges ( ACA) 

 

20A / 200A / 2000A / 30A / 300A / 3000A

 

Meter can cooperate the universal current probes

Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe ( CP-1201) , AC to DC 9V Adapter, 2GB SD Memory card and Carrying bag

Measurement: 

 

V ( phase-to-phase) 

 

V ( phase-to-ground) 

 

A ( phase-to-ground) 

 

KW / KVA / KVAR / PF ( phase) 

 

KW / KVA / KVAR / PF ( system) 

 

KWH / KVAH / KVARH / PFH ( system) 

 

Phase Angle

 

Harmonics display ( 1-50th order) 

Simultaneous display of Harmonics and Waveform

Display of Waveform with Peak Values

Analysis of Total Harmonic Distortion ( THD) 

Graphic Phase diagram with 3-Phase system parameters

3 Phase Voltage or Current Unbalanced Ratio ( VUR, VIR) and Unbalanced Factor

Calculated Unbalanced Current through Neutral Line ( In) 

Capture Transient events ( including Dip, Swell and Outage) with programmable threshold ( % ) 

Programmable CT ratio ( 1 to 600) and PT ratio ( 1 to 1000) 

ACV input impedance is 10M ohms

Safety Standard: IEC 1010, CAT III 600V

Built-in clock and Calendar, real time data record with SD memory card, sampling time set from 2 to 7200 seconds. Just slot in the SD card into the computer, it can download all the measured valued with the time information ( year, month, date, hour, minute, second) to the Excel directly, then user can make the further data analysis by themselves

Powered by AA ( UM-3) DC 1.5V x 8 batteries ( Alkaline type) of DC 9V adapter

Computer data output, can cooperate with optional USB cable ( USB-01) , RS-232 cable ( UPCB-02) and Data Acquisition software ( SW-811) 

Optional current probes: CP-1201, CP-2000, CP-200, CP-3000

User can order the meter only ( without the current probes) with the special request as intend to cooperate their own current probe

Patented

 

No reviews found