ENKO (ENCO) Battery Charger

Write a review
$44.29
34363
In stock
+
ENKO or ENCO EBC Diesel Generator Chargers
 
Product Introduction:
EBC series chargers with European EMC and LVD standards, are used to charge a variety of wet batteries or jelly diesel engines and are perfectly suited to industrial environments and have a wide range of applications in the diesel generator industry.
 
12 volts 5 amps (EBC1205):
Output voltage: 13.8 volts
Output current: 5.0 amps
Short circuit current: 5.5 amps
10 amp slow reversing fuse
Yield: 80%
 
12 volts 10 amps (EBC1210):
Output voltage: 13.8 volts
Output current: 10.0 amps
Short circuit current: 11 amps
15 amp reverse connection fuse
Yield: 80%
 
24 volts 5 amps (EBC2405):
Output voltage: 27.6 volts
Output current: 5.0 amps
Short circuit current: 5.5 amps
10 amp slow reversing fuse
Yield: 80%
 
24 volts 10 amps (EBC2410):
Output voltage: 27.6 volts
Output current: 10.0 amps
Short circuit current: 11 amps
15 amp reverse connection fuse
Yield: 82%
 
Common features of ENKO brand EBC chargers:
Has a short circuit amp limiting system (110% output current)
Includes internal diode for reverse polarity protection
Has a series fuse in the terminal to prevent the dangers of incorrect connection of pliers
With boost charge capability (increase of output voltage - decrease of output amps up to 50%)
Ability to operate in a wide range of input voltage (150 to 300 volts phase to zero)
Operation at full power up to 60 ° C
Ability to install identical models to increase voltage / output current (series / parallel)
Has a transistor warning output (input to the control panel of diesel generator with external relay)
Can be installed on the panel and...(There is a screw on the back of the charger.)
 
Guide for choosing the right wire to connect the chargers to the battery:
5 amp models (1205 and 2405): length 5 meters size 1.5 miles and length 10 meters size 2 miles
10 amp models (1210 and 2410): length 5 meters size 2 miles and length 10 meters size 2.5 miles
*It is recommended that the length of the wires should not be more than 10 meters
 
Indicator LED guide:
Green: Normal performance
Red: Charger input has no power / charger is not connected to the battery
Green + Red: Reverse connection / external fuse blown

No reviews found